Plan Review Notes For Permit 00070815 |
Permit Number |
00070815 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | PROVISO:******************************** | | 1.DUCT MATERIAL SCHEDULE REQUIRED. | | 2.PROVIDE ENERGY EFFICIENCY RATING PER | | FLORIDA EFFICIENCY CODE. | | 3.CLEARANCE OF EXHAUST AIR FROM OUTSIDE | | AIR INTAKE MIN. 10FT. PER 1997 SMC 506.1 | | NOTE:*********************************** | | SEPERATE PERMIT REQUIRED FOR HOOD, GAS, | | FIRE-SUPPRESSION SYSTEM, WALK-IN COOLER/ | | FREEZERS. |
|