Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) NO FIRE SPRINKLER PLANS OR
 HYDRAULIC CALCULATIONS PROVIDED IN
 DRAWINGS.
 2) GAS INSTALLATION TO COMPLY WITH
 NFPA 54.
 3) PROVIDE COMPLETE SHOP DRAWINGS FOR
 THE INSTALLATION OF THE HOOD, DUCT
 AND EXTINGUISHING SYSTEM. WET CHEMICAL
 EXTINGUISHING SYSTEMS ARE ONLY SYSTEMS
 PERMITTED.
 4) ALL DOORS USED FOR EXITING TO BE
 EQUIPPED WITH PANIC HARDWARE. FIRE EXIT
 HARDWARE TO BE INSTALLED ON FIRE DOORS.
 5) PROVISIONS TO BE MADE FOR AT LEAST
 TWO HANDICAPPED PERSONS.
 6) DEFINE WAITING AREA. WAITING AREAS
 CANNOT INTERFERE WITH EXITING.
 7) MAIN ENTRY MUST BE CAPABLE OF
 PROVIDING EXITING FOR AT LEAST 50
 PERCENT OF OCCUPANT LOAD.
 8) DEFINE RAMPS AND STAIRS. ANY CHANGE
 IN ELEVATION LESS THAN 21" SHALL BE BY
 RAMPS.
 9) EXPLAIN EXITING ROUTES.
 10) PROVIDE FLAMESPREAD DOCUMENTATION ON
 BOOTHS AND BRANCHES.
 11) SEAT COUNTS ON PAGE ID-1 AND ID-8
 DO NOT MATCH.
 12) EXPLAIN PLATFORMS.
 13) HOW IS THE BASE BUILDING FIRE ALARM
 SYSTEM HEARD IN TENANT SPACE.
 14) PORTABLE FIRE EXTINGUISHERS REQUIRED