Plan Review Notes
Plan Review Notes For Permit 00070813
Permit Number 00070813
Review Stop B
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00TRUSS PLANS: DENIED 12/12/2000 JW
 TC-4 ARCH PLANS SHOW A 3 POINT BEARING
 TRUSS VS TRUSS PLANS A 2 POINT BEARING
 TRUSS.
 ARCH PLANS A5 & A6 INDICATE BEARING WALL
 WITH HANGERS VS A 2 POINT TRUSS IN THE
 TRUSS PLAN.
 ARCH SHEET 2/A5 HANGER NOT IDENTIFIED
 ARCH SHEET INDICATES THAT TRUSS HANGER
 BY TRUSS MGR VS TRUSS PLAN INDICATES "K"
 BY BUILDER.H2,H3,T1 & M12.
 TRUSS H-8 3 POINT VS SHEET A-6 2 POINT.
 TRUSS H-7 3 POINT VS SHEET A-6 2 POINT.
 TRUSS H-6 UPLIFT LOADS NOT CONSISTANT
 WITH A-6.TRUSS SHEET H6 WHAT TYPE OF
 CONNECTION AT POINT 22/14?
 POINT #227899
 POINT #142183
 POINT 22 CRUSHING VALUES?