Plan Review Notes For Permit 00070798 |
Permit Number |
00070798 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | APPROVED WITH PROVISO: | | 1-PROVIDE PRODUCT APPROVAL FOR: | | -BUTT GLAZING SYSTEM. | | -CUSTOM MADE KITCHEN WINDOW ASSEMBLY. | | -ENTRY DOORS W/ TRANSOM ABOVE ASSEMBLY. | | -FRENCH DOORS W/ TRANSOM ABOVE ASSEMBLY | | (SEE COMMENTS ON SUBMITTAL). | | -S.G.D. WITH TRANSOM ABOVE ASSEMBLY. | | (SEE COMMENTS ON SUBMITTAL). | | -GARAGE DOORS PRODUCT APPROVALS THAT | | MEET THE DESIGN PRESSURES CALCULATED | | BY THE ARCHITECT. | | 2-COMPLETELY SPECIFY CEILING CONSTRUCT'N | | AT ENTRY AND REAR PORCHES, INCLUDING | | FASTENER TYPES AND SPACING. SECTION | | 2504 SBC 1997. | | 3-STORM PANELS TO BE UNDER A SEPARATE | | PERMIT. (NO INFO. GIVEN AT THIS TIME). | | 4-TRUSS DRAWINGS: | | -PROVIDE COMPLETE SET OF ENG'D TRUSS | | DRAWINGS. | | -ENGINEER TO SIGN, SEAL AND DATE TRUSS | | LAYOUT AS WELL. | | -ARCHITECT TO REVIEW ALL TRUSS DRAWINGS | | PRIOR TO SUBMITTAL TO THIS OFFICE. | | | | | | | | | | NOTES: | | -PLEASE SUBMITINFORMATION REQUIRED ON | | PROVISO PRIOR TO CONSTRUCTION OR | | INSTALLATION TO AVOID DELAYS. |
|