2002-03-06 00:00:00**********INSUFFICIENT
 INFORMATION******PLEASE PROVIDE THE
 FOLLOWING INFORMATION AND RESUBMIT FOR
 REVIEW.
  
 1] PERMIT APPLICATION INDICATES A 150
 AMP SERVICE IS TO BE INSTALLED.PLEASE
 PROVIDE A RISER DIAGRAM FOR
 SAME.INCLUDE AIC
  
 2] PROVIDE A LOAD CALCULATION AND PANEL
 SCHEDULES AS PER 215-5.
  
 3] GFI'S PER 210-52(E).
  
 4] COMPLY WITH NFPA-72 2-2.1.1.1.(BED
 ROOM SMOKE DETECTORS).
  
 5] BED ROOM,BATH ROOM,AND KITCHEN
 RECEPTACLES AND CIRCUITS ARE NOT IN
 COMPLIANCE WITH NEC ARTICLES
 210-52,210-11(C)(3) & 210-52(B)&(C)
 RESPECTIVELY.PLEASE BE MORE SPECIFIC IN
 THE SCOPE OF WORK TO BE DONE.
  
 6] IF A/C IS TO BE INSTALLED,PLEASE SHOW
 UNIT LOCATIONS AND INDICATE BRANCH
 CIRCUIT WIRING SIZE & TYPE.(ALSO GFI
 LOCATION AT CU.).
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/659-8096 EXT.8392