Plan Review Notes For Permit 00070639 |
Permit Number |
00070639 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | DENIED: | | 1.PROVIDE AIR BALANCE SCHEDULE AS PER | | 1997 SMC 501.2... | | 2.REQUIRE DUCT MATERIAL SCHEDULE. | | 3.EXHAUST FAN DETAIL REQUIRED ON PLANS. | | 4.PROVIDE ENERGY EFFFICIENCY RATING OF | | THE AHU-1 AS PER FLORIDA ENERGY EFFICI- | | ENCY CODE. | | 5.PROVDE CFM VALUE OF AHU TO MATCH THE | | TOTAL OF CFM ON THE PLANS 6550 CFM... |
|