Plan Review Notes
Plan Review Notes For Permit 00070639
Permit Number 00070639
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED:
 1.PROVIDE AIR BALANCE SCHEDULE AS PER
 1997 SMC 501.2...
 2.REQUIRE DUCT MATERIAL SCHEDULE.
 3.EXHAUST FAN DETAIL REQUIRED ON PLANS.
 4.PROVIDE ENERGY EFFFICIENCY RATING OF
 THE AHU-1 AS PER FLORIDA ENERGY EFFICI-
 ENCY CODE.
 5.PROVDE CFM VALUE OF AHU TO MATCH THE
 TOTAL OF CFM ON THE PLANS 6550 CFM...