Plan Review Notes For Permit 00070639 |
Permit Number |
00070639 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) FIRE SPRINKLER PLANS ALREADY HAVE | | REVIEWED AND APPROVED BY FIRE RESCUE. | | 2) INTERIOR FINISH SHALL BE CLASS A OR | | B. | | 3) EXITING PERMITTED THROUGH STOCKROOM | | IF THE FOLLOWING CONDITIONS EXIST: | | NOT MORE THAN 50 PERCENT OF EXIT ACCESS | | IS PROVIDED THROUGH STOCKROOM, AISLE OF | | AT LEAST 44" WIDE IS PRESENT, AISLE IS | | KEPT AT 44" WIDE, STOCKROOM NOT SUBJECT | | TO LOCKING. | | 4) PORTABLE FIRE EXTINGUISHER(S) | | REQUIRED. |
|