Plan Review Notes For Permit 00070448 |
Permit Number |
00070448 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) PROVIDE FIRE ALARM SYSTEM SHOP | | DRAWINGS FOR FIRE ALARM EQUIPMENT | | SHOWN ON DRAWINGS. | | 2) FITTING ROOM AND BATHROOM DOORS | | CANNOT INTERFERE WITH ACCESS TO EXIT | | DOOR LEADING INTO STOCKROOM. | | 3) EXITING PERMITTED THROUGH STOCKROOM | | IF THE FOLLOWING CONDITIONS EXIST, | | NOT MORE THAN 50 PERCENT OF EXIT ACCESS | | IS THROUGH STOCKROOM, THE DOOR LEADING | | TO STOCKROOM CANNOT BE LOCKED, AISLE | | OF AT LEAST 44" WIDE BE PRESENT WITHIN | | STOCKROOM, THIS 44" AISLE BE MAINTAINED. | | 4) PORTABLE FIRE EXTINGUISHERS ARE | | REQUIRED. |
|