Plan Review Notes For Permit 00070448
Permit Number 00070448
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:001) PROVIDE FIRE ALARM SYSTEM SHOP
 DRAWINGS FOR FIRE ALARM EQUIPMENT
 SHOWN ON DRAWINGS.
 2) FITTING ROOM AND BATHROOM DOORS
 CANNOT INTERFERE WITH ACCESS TO EXIT
 DOOR LEADING INTO STOCKROOM.
 3) EXITING PERMITTED THROUGH STOCKROOM
 IF THE FOLLOWING CONDITIONS EXIST,
 NOT MORE THAN 50 PERCENT OF EXIT ACCESS
 IS THROUGH STOCKROOM, THE DOOR LEADING
 TO STOCKROOM CANNOT BE LOCKED, AISLE
 OF AT LEAST 44" WIDE BE PRESENT WITHIN
 STOCKROOM, THIS 44" AISLE BE MAINTAINED.
 4) PORTABLE FIRE EXTINGUISHERS ARE
 REQUIRED.