Plan Review Notes For Permit 00070248 |
Permit Number |
00070248 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | **************PROVISO **************** | | | | 1)NOTE:PLEASE SUBMIT THE AIC RATING OF | | EQUIPMENT MAINS/PANELS. MUST BE RATED | | FOR THE AVAILABLE FAULT CURRENT.110-9 | | | | 2)NOTE: PLEASE NOTE THAT MAIN PANEL IS | | SHOWN AS 8 CIRCUIT? IS THERE GOING TO BE | | ANOTHER PANEL OR IS THIS PANEL HAVE MORE | | CIRCUITS? | | | | 3)NOTE: PLEASE SUBMIT A REVISED PANEL | | SCHEDULE AND INCLUDED THE REQ`D DEDICAT- | | -ED BATH(S) CIRCUIT(S). PER 210-11-C-3 | | | | 4)NOTE: PLEASE NOTE THAT ALL OUTLETS | | SERVING KITCHEN COUNTERSPACE ARE TO BE | | GFI/GFI PROTECTED. 210-8-A-6. | | PLEASE SHOW. | | | | 5)NOTE: PLEASE NOTE THE REQ`MENTS FOR | | GFI OUTLETS FRONT AND BACK OF DWELLING | | AS PER 210-52E | | | | 6)NOTE: PLEASE NOTE THE MISSING OUTLET | | IN BEDROOM. AS PER 210-52 | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW BEFORE ROUGH ELECTRICAL INSPECT- | | -ION IS CALLED IN. IF THERE ARE ANY | | QUESTIONS PLEASE CALL 561-659-8096 EXT | | 8372. |
|