2001-01-08 00:00:00**************PROVISO ****************
  
 1)NOTE:PLEASE SUBMIT THE AIC RATING OF
 EQUIPMENT MAINS/PANELS. MUST BE RATED
 FOR THE AVAILABLE FAULT CURRENT.110-9
  
 2)NOTE: PLEASE NOTE THAT MAIN PANEL IS
 SHOWN AS 8 CIRCUIT? IS THERE GOING TO BE
 ANOTHER PANEL OR IS THIS PANEL HAVE MORE
 CIRCUITS?
  
 3)NOTE: PLEASE SUBMIT A REVISED PANEL
 SCHEDULE AND INCLUDED THE REQ`D DEDICAT-
 -ED BATH(S) CIRCUIT(S). PER 210-11-C-3
  
 4)NOTE: PLEASE NOTE THAT ALL OUTLETS
 SERVING KITCHEN COUNTERSPACE ARE TO BE
 GFI/GFI PROTECTED. 210-8-A-6.
 PLEASE SHOW.
  
 5)NOTE: PLEASE NOTE THE REQ`MENTS FOR
 GFI OUTLETS FRONT AND BACK OF DWELLING
 AS PER 210-52E
  
 6)NOTE: PLEASE NOTE THE MISSING OUTLET
 IN BEDROOM. AS PER 210-52
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW BEFORE ROUGH ELECTRICAL INSPECT-
 -ION IS CALLED IN. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 561-659-8096 EXT
 8372.