2001-01-08 00:00:00HOW CAN YOU CARRY 454,000 BTU'S ON A
 3/4" LINE CONNECTED TO THE METER?
  
 MY CALCULATIONS SHOW 66' TO THE MOST
 REMOTE OUTLET.EXPLAIN HOW YOU CALCULATE
 102'.
  
 SIZE ALL CUT SECTIONS OF PIPE.SEE LINE
 TO POOL HEATER.
  
 REVIEW AND REVISE DRAWING TO COMPLY W/
 SGC.