Plan Review Notes For Permit 00070085 |
Permit Number |
00070085 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | PROVISO: | | 1. DUCT SMOKE DETECTOR SHALL BE LOCATED | | IN SUPPLY AIR STREAM PER NFPA 90A 4-4 OR | | IN THE RETURN AIR DUCT PRIOR TO ANY MIX- | | ING OF OUTSIDE AIR PER 1997 SMC THE | | DETAIL ON M-1 SHOWS DUCT DETECTOR NOT | | SENSING THE RETURN DROP FROM THE STORE | | ROOM AND THIS HAS TO BE PROTECTED BY THE | | DUCT DETECTOR ALSO |
|