Plan Review Notes
Plan Review Notes For Permit 00070085
Permit Number 00070085
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVISO:
 1. DUCT SMOKE DETECTOR SHALL BE LOCATED
 IN SUPPLY AIR STREAM PER NFPA 90A 4-4 OR
 IN THE RETURN AIR DUCT PRIOR TO ANY MIX-
 ING OF OUTSIDE AIR PER 1997 SMC THE
 DETAIL ON M-1 SHOWS DUCT DETECTOR NOT
 SENSING THE RETURN DROP FROM THE STORE
 ROOM AND THIS HAS TO BE PROTECTED BY THE
 DUCT DETECTOR ALSO