Plan Review Notes For Permit 00070055 |
Permit Number |
00070055 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************* PROVISO ***************** | | | | 1)NOTE: PLEASE SUBMIT AIC RATING OF MAIN | | -S. THIS WAS ASKED FOR ON FIRST SET OF | | REVIEW NOTES. PER 110-9 AND 215-5. | | ALSO PLEASE CLARIFY THAT ALL BRANCH | | BRKRS ARE SHOWN AT 22,000 AIC IN PANEL? | | IS THIS CORRECT? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW BEFORE FINAL ELECTRICAL INSPECT- | | -ION IS CALLED IN,.IF THERE ARE ANY | | QUESTIONS PLEASE CALL, | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | 659-8096 EXT 8372 |
|