Plan Review Notes
Plan Review Notes For Permit 00070055
Permit Number 00070055
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00PROVISO;
 DRINKING FOUNTAIN MUST BE PART OF THE
 PLUMBING SYSTEM. 1994 STANDARD PLUMBING
 CODE CHAPTER 4 (MINIMUM FIXTURES) TABLE
 407.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved