2001-01-08 00:00:00***************PROVISO******************
 1)OVERFLOW LINE SHALL DISCHARGE TO
 STORM.
  
 2)SUBMIT ALL SECTION DETAILS NOTED ON
 SHEET W1.3.
  
 3)PIPE SIZES SHOWN ON SHT.W1.3 DON'T
 CORRELATE W/SIZES NOTED IN DETAIL "C"
 ON W4.8.
  
 4)SIZE ALL PIPNG ON SHT.W2.2 AND SIZE
 PIPING ON ALL DETAILS.
  
 5)SUBMIT ALL APPLICABLE SHEETS FOR
 REVIEW.SOME NOTED DETAILS ARE NOT ON THE
 PLANS.SUBMIT ALL DETAILS FOR REVIEW ON
 AS-BUILTS.
  
 6)INDICATE MAKE,MODEL AND TYPE OF
 BACKFLOW PREVENTION DEVICE SHOWN IN WET
 WALL FOUNTAIN ROOM.