Plan Review Notes
Plan Review Notes For Permit 00070034
Permit Number 00070034
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT ALL LISTED SHEETS FOR PLAN REVIEW
 THAT PERTAIN TO THE WET WALL FOUNTAINS.
 COUNTYWIDE AMENDMENTS TO SPC SEC.104.2.1
  
 SHT.W0.0-NOTE (5)(G),SHT.W6.0-(C)(3)-
 DELETE REFERENCE TO UNIFORM PLUMBING
 CODE AND INSERT STANDARD PLUMBING CODE.
 COMPLY W/SPC SEC.101.1,101.2.
  
 SIZE ALL PIPING TO VAULT ON SHT.W2.2.
 AND SIZE PIPING ON ALL DETAILS.
  
 PIPE SIZES SHOWN ON SHT.W1.3 DON'T
 CORRELATE W/SIZES SHOWN IN DETAIL "C"
 ON W4.8.
  
 INDICATE MAKE,MODEL AND TYPE OF BFP
 DEVICE SHOWN IN WET WALL FOUNTAIN
 EQUIPMENT ROOM.