Plan Review Notes
Plan Review Notes For Permit 00070034
Permit Number 00070034
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00FAILED
 1.0
 DRAWINGS SUBMITTED DO NOT SHOW TIE IN
 OFF OKEECHOBEE BLVD FOR WATER AND SEWER.
 2.0
 PVC PIPINGAND CONDUITS MUST BE GROUPED
 &SLEEVED TOGETHER WHEN CROSSING ROSEMARY
 AVENUE.MUST KEEP 1O'MIN AWAY FROM EX. WM
 3.0
 DISCHARGE FROM THE SYSTEM SHALL BE TIED
 TO SANITARY SEWER AND NOT TO THE DRAINGE
 AS CALLED OUT.
 4.0
 NO METERS OR BACKFLOWS ARE SHOWN IN ANY
 DRAWING.
 5.0
 ALL WORK PERFORMED ALONG OKEECHOBEE
 BLVD MUST BE DONE UNDER A PERMIT FROM
 FDOT.
 6.0
 PLEASE PROVIDE LOCATION OF ALL UTILITES
 WHERE TAPPING WILL OCCUR OR ALONG ANY
 CITY ROW WHERE WORK WILL BE PERFORM.
 THIS WILL AVOID ANY CONFLICTS IN THE
 FIELD.
 7.0
 TWO SETS OF PRINTS OF THE TAP WILL HAVE
 TO BE SUBMITTED TO MANNY GONZALEZ
 CITY OF WEST PALM BEACH 1000 45TH ST
 WEST PALM BEACH, FL 33409
 561-659-8040.
 8.0
 SHOPDRAWINGS WILL BE REQUIRED ON ANY
 ITEMS INSTALLED OUT IN THE ROW. SUBMITT
 2 COPIES FOR APPROVAL.
 9.0
 FOR SANITARY SEWER SERVICES A CLEAN-OUT
 IS REQUIRED EVERY 75L.F. AND ONE MUST
 BE PROVIDED JUST INSIDE OF THE R.O.W.
 LINE ON PRIVATE PROPERTY.
 10.0
 PLEASE PROVIDE MORE DETAIL OF WHERE THE
 FOUNTAINS FALL WITHIN THE ROW AND EXIST.
 UTILIES.