Plan Review Notes
Plan Review Notes For Permit 00070033
Permit Number 00070033
Review Stop ENG
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00FAILED
 1.00
 PLEASE PROVIDE PROPERTY INFORMATION
 ON WHICH THESE FOUNTAINS FALL IN.
 2.00
 DISCHARGE WATER NEEDS TO GO TO SANITARY
 SEWER, PLEASE PROVIDE PLAN WHERE THIS
 CONNECTION IS MADE.
 3.00
 NO WATER TAPS OR SERVICE CONNECTION
 ARE SHOWN ON ANY PLAN. PLEASE PROVIDE
 4.00
 PLEASE SHOW ALL UTILITIES THAT FALL
 WHERE FOUNTAIN LINES WILL BE INSTALLED.
 THIS WILL AVOID ANY CONFLICTS IN THE
 FIELD AND WILL HELP IN FUTURE
 MAINTENANCE OF THE FOUNTAIN.
 5.00
 PLEASE PROVIDE LOCATION OF ALL UTILITIES
 WHERE TAPPING WILL OCCUR OR ALONG ANY
 CITY ROW WHERE WORK WILL BE PERFORMED.
 6.00
 TWO SETS OF PRINTS OF THE TAP WILL HAVE
 TO BE SUBMITTED TO MANNY GONZALEZ
 CITY OF WEST PALM BEACH 1000 45TH STREET
 WEST PALM BEACH, FL 33409 (SUITE 9)
 561-659-8040
 7.00
 SHOP DRAWINGS WILL BE REQUIRED ON ANY
 ITEMS INSTALLED OUT IN THE ROW.
 SUBMITT TWO COPIES TO MANNYG. FOR
 APPROVAL.
 8.00
 FOR SANITARY SEWER SERVICES A CLEAN-OUT
 IS REQUIRED EVERY 75L.F. AND ONE MUST
 BE PROVIDED JUST INSIDE OF THE R.O.W.
 LINE ON PRIVATE PROPERTY.