Plan Review Notes For Permit 00061789 |
Permit Number |
00061789 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) PROVIDE SHOP DRAWINGS FOR FIRE ALARM | | EQUIPMENT SHOWN IN TENANT SPACE. | | 2) EXITING PERMITTED THROUGH STOCKROOM | | ONLY IF THE FOLLOWING CONDITIONS EXIST | | NOT MORE THAN 50 PERCENT OF EXIT ACCESS | | IS PERMITTED THROUGH STOCKROOM, | | STOCKROOM DOOR CANNOT BE LOCKED, | | AISLE THROUGH STOCKROOM TO BE AT LEAST | | 44" WIDE, AISLE TO BE MAINTAINED AT | | 44" WIDE CONDITION. |
|