Plan Review Notes For Permit 00061786 |
Permit Number |
00061786 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ****************PROVISO***************** | | 1)SHT.A1-DRESSING ROOM SHALL COMPLY W/ | | FACBC SEC.4.35.4.BENCH SHALL BE LOCATED | | ALONG THE LONGER DIMENSION WALL. | | | | 2)WATER CLOSETS NOT PERMITTED WET VENTS | | PER COUNTYWIDE AMENDMENTS TO SPC SEC. | | 911.1.1.SUBMIT REVISED SANITARY RISER | | PRIOR TO PLUMBING INSPECTION. | | | | 3)POINT OF USE WATER HEATER SHALL BE | | LISTED PER SPC 503.3. | | | | 4.)HANDICAP ACESSIBLE TOILET ROOMS SHALL | | BE INDELIBLY POSTED FOR THE INTENDED | | USE,BE ON AN ACCESSIBLE ROUTE,AND | | AVAILABLE TO PATRONS DURING NORMAL | | OPERATING HOURS.ACCESSIBLE ROUTE SHALL | | BE CLEARLY DEFINED ON THE PLANS. | | FACBC SECS.4.1.2(7),4.1.3.(16),4.1.3(11) | | 4.2.1.,4.3.1,4.3.2(3),4.3.3. | | SPC SEC.407.2.2. |
|