Plan Review Notes For Permit 00061755 |
Permit Number |
00061755 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ***************** PROVISO ************** | | | | 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR | | BOTH MAIN DISCONNECT AND PANEL. | | MAINS/PANELS MUST BE RATED FOR THE | | AVAILABLE FAULT CURRENT PER 110-9 | | | | PLEASE SUBMIT FOR REVIEW BEFORE FINAL | | ELECTRICAL INSPECTION IS CALLED IN. | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | 561-659-8096 EXT 8372 |
|