Plan Review Notes
Plan Review Notes For Permit 00061755
Permit Number 00061755
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00***************** PROVISO **************
  
 1)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 BOTH MAIN DISCONNECT AND PANEL.
 MAINS/PANELS MUST BE RATED FOR THE
 AVAILABLE FAULT CURRENT PER 110-9
  
 PLEASE SUBMIT FOR REVIEW BEFORE FINAL
 ELECTRICAL INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 561-659-8096 EXT 8372