2001-01-08 00:00:00SECOND CHECKLIST:
 (SAME ITEMS REQUESTED ON 1ST CHECKLIST)
  
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 BRING RECEIPT AND STAMPED DRAWINGS.
 2-REVISE LOAD REQUIREMENTS FOR ATTIC
 STORAGE. 30 PSF LIVE LOAD. SEE TABLE
 1604.1 SBC 1997.
 3-PROVIDE SAFETY GLASS AT FAMILY ROOM,
 LIVING ROOM AND MASTER BATH. SEE PLANS
 AND SECTION 2405.2 SBC 1997.
 4-PROVIDE COMPLETE AHU HANGING DETAILS.
 INCLUDE FASTENERS TYPES AND SIZES.
 DETAIL SHOWN ON SHEET A5 DOESN'T APPLY
 5-PROVIDE COMPLETE SPECIFICATIONS/DETAIL
 FOR CEILING CONSTRUCTION AT ENTRY AND
 REAR PORCHES. INCLUDE FASTENER TYPES
 AND SPACING. SECTION 2504 SBC 1997.
 6-FOOTING F2 TO HAVE 16" MINIMUM DEPTH
 AS PER SECTION 1804.1.9 OF CITY
 AMENDMENTS AND SEC 1804.1.3 SBC 1997.
 7-ROOF FRAMING PLAN: SOME TRUSS GIRDERS
 ARE SHOWN WITHOUT A SUPPORTING POST TO
 TRANSFER THE LOAD TO THE FOOTING.
 SPECIFY POSTS AND TOP AND BOTTOM
 CONNECTORS. ALSO, VERIFY IF CONCRETE
 PAD WILL BE REQUIRED TO SUPPORT THE
 LOAD. SEC 104.2.2 CITY AMENDMENTS.
 8-PROVIDE DETAIL/SPECS SHOWING HOW ARE
 OPENINGS DESIGNED TO RECEIVE STORM
 PANELS. DRAWINGS SHOW PRECAST LINTELS,
 BUT WHAT ABOUT WINDOW SILLS?
 THIS WILL DETERMINE THE TYPE OF ANCHOR
 AND SPACING REQUIRED TO INSTALL THE
 STORM PANEL.
 9-PROVIDE COMPLETE CONSTRUCTION DETAILS
 FOR ARCHED OPENINGS.
 SECTION 104.2.2 CITY AMENDMENTS.
 10-REVISE SOIL TEST REPORT. WE FOLLOW
 THE 1997 SBC, NOT 1994.
 -ALSO, PROVIDE COPIES OF THE TESTS
 PERFORMED AS PER TABLE 1804.2.7.3 OF
 CITY AMENDMENTS.
 11-PROVIDE COMPLETE BUCK DETAILS FOR
 INSTALLATION OF DOORS AND WINDOWS.
 INCLUDING THE STRUCTURAL BUCK DETAIL
 TO SUPPORT THE GARAGE DOORS AND THE
 POCKET TYPE SLIDING GLASS DOORS.
 NOTE: SEE PRODUCT APPROVALS FOR THE
 SIZE OF BUCK REQUIRED.
 12-STORM PANELS:
 -PROVIDE COMPLETE INFORMATION FOR THE
 INSTALLATION OF STORM PANELS,INCLUDING
 PRODUCT APPROVAL, ATTACHED SAMPLE OF
 INSTALLATION SCHEDULE AND KEY PLAN AND
 PROPER IDENTIFICATION OF MOUNTING
 CONDITIONS AND ANCHORS TO BE USED.
 NOTE:THIS INFORMATION MAY BE SUBMITTED
 LATER UNDER A SEPARATE APPLICATION.
 13-PROVIDE CURRENT PRODUCT APPROVAL FOR:
 -BUTT GLAZING SYSTEM AS SHOWN ON PLANS.
 -POCKET SLIDING GLASS DOORS.
 -FIXED WINDOWS OF SIZES AS SHOWN LIVING
 ROOM AND FAMILY ROOM.
 -WINDOW MULLIONS.
 -ARCHED WINDOWS.
 -ENTRY DOORS.
 14-SEE ADDITIONAL COMMENTS ON PLANS,
 INCLUDING COMMENTS BY THE OTHER TRADES
 15-HIGHLIGHT FASTENING METHOD AND SYSTEM
 TO BE USED IN ROOF TILE PRODUCT
 APPROVAL.
 16-APPLICATION FOR PERMIT MUST BE FILLED
 COMPLETELY AND SIGNED BY THOSE SUBS
 WHO APPLY IN THE ORIGINAL APPLICATION.
 17-GENERAL CONTRACTOR TO UPDATE LICENSE
 AND INSURANCE.
  
 NOTES:
 -IT LOOKS LIKE THE ARCHITECT REVIEWED
 OUR MARKED SET AND EVEN MADE SOME
 COMMENTS. BUT, UNFORTUNATELY THE SETS
 THAT WERE RE-SUBMITTED AREN'T THE
 REVISED ONES. PLEASE RE-SUBMIT THOSE
 DRAWINGS AND DON'T FORGET TO INCLUDE
 THIS MARKED SET IN ORDER TO EXPEDITE
 THE REVIEW PROCESS.
 -IF YOU HAVE ANY QUESTIONS, PLEASE FEEL
 FREE TO CONTACT JULIO GOMEZ AT 659-8096
 EXT. 8232.