Plan Review Notes
Plan Review Notes For Permit 00061630
Permit Number 00061630
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CHECKLIST:
 1-PAY IMPACT FEES TO PALM BEACH COUNTY.
 2-REVISE LOAD REQUIREMENTS FOR ATTIC
 STORAGE. 30 PSF LIVE LOAD. SEE TABLE
 1604.1 SBC 1997.
 3-PROVIDE SAFETY GLASS AS REQUIRED AT
 FAMILY ROOM, LIVING ROOM AND MASTER
 BATH. SECTION 2405.2 SBC 1997.
 4-PROVIDE COMPLETE AHU HANGING DETAILS.
 INCLUDE FASTENERS TYPES AND SIZES.
 DETAIL SHOWN ON SHEET A5 DOESN'T APPLY
 TO THIS HOUSE. SECTION 104.2.2 CITY
 AMENDMENTS TO SBC 1997.
 5-PROVIDE COMPLETE SPECIFICATIONS/DETAIL
 FOR CEILING CONSTRUCTION AT ENTRY AND
 REAR PORCHES. INCLUDE FASTENERS TYPES
 AND SPACING. SECTION 2504 SBC 1997.
 6-FOOTING F2 TO HAVE 16" MINIMUM IN
 DEPTH AS PER SECTION 1804.1.9 OF CITY
 AMENDMENTS AND SEC. 1804.1.3 SBC 1997.
 7-ROOF FRAMING PLAN: SOME TRUSS GIRDERS
 ARE SHOWN WITHOUT A SUPPORTING POST TO
 TRANSFER THE LOAD TO THE FOOTING.
 SPECIFY POSTS AND TOP AND BOTTOM
 CONNECTORS. VERIFY IF CONCRETE PAD
 REQUIRED TO CARRY THE LOAD.
 SECTION 104.2.2 CITY AMENDMENTS.
 8-PROVIDE DETAIL/SPECS SHOWING HOW ARE
 OPENINGS DESIGNED TO RECEIVESTORM
 PANELS. DRAWINGS SHOW PRECAST LINTELS,
 BUT WHAT ABOUT WINDOW SILLS?
 THIS WILL DETERMINE THE TYPE OF ANCHOR
 AND SPACING REQUIRED TO INSTALL THE
 STORM PANEL.
 9-PROVIDE COMPLETE DETAIL/SPECS FOR
 CONSTRUCTION OF ARCHED OPENINGS.
 SECTION 104.2.2 CITY AMENDMENTS.
 10-PROVIDE SURVEY SHOWING NEW BUILDING
 LAYOUT.
 11-PROVIDE SOIL TEST REPORT AS PER SEC.
 1804.2.7.3 OF CITY AMENDMENTS.
 12-PROVIDE COMPLETE BUCK DETAILS FOR
 INSTALLATION OF DOORS AND WINDOWS.
 INCLUDING THE STRUCTURAL BUCK DETAIL
 FOR GARAGE DOORS AND SGD POCKET TYPE.
 NOTE: SEE PRODUCT APPROVALS FOR
 REQUIRED BUCK SIZE.
 13-STORM PANELS:
 -CLARIFY WHICH PRODUCT APPROVAL IS
 GOING TO BE USED. SBCCI OR DADE COUNTY
 AND PROVIDE COMPLETE DRAWINGS FOR
 EITHER ONE.
 -SBCCI PRODUCT APPROVAL REPORT AND
 DRAWINGS DON'T MATCH. SEE PAGE TWO OF
 PRODUCT APPROVAL FOR APPROVED DRAWINGS
 -PROVIDE A COMPLETE INSTALLATION SCHED.
 AS PER CITY SAMPLE ATTACHED AND KEY
 PLAN.
 NOTE: KEEP IN MIND THAT ANCHOR TYPE
 AND SPACING IS TO BE SELECTED ACCORD'G
 TO THE DESIGN PRESSURES,EDGE DISTANCE,
 PANEL SPAN, MEAN ROOF HEIGHT,CONNECT'N
 TYPE AND STRUCTURE TO BE ATTACHED TO.
 (THIS BUILDING IS MASONRY CONSTRUCTION
 NOT 3000PSF CONCRETE).
 14-PROVIDE CURRENT PRODUCT APPROVAL FOR:
 BUTT GLAZING SYSTEM AS SHOWN ON PLANS,
 GARAGE DOORS (DADE COUNTY OR SBCCI, NO
 BROWARD COUNTY), SLIDING GLASS DOORS
 (POCKET TYPE AS SHOWN ON PLANS), FIXED
 WINDOWS OF SIZES AS SHOWN ON LIVING RM
 AND FAMILY RM,WINDOW MULLIONS, ARCHED
 WINDOWS, ENTRY DOORS (IF SITE SPECIFIC
 THEN THE PRODUCT APPROVAL FORM SHALL
 BE SIGNED, SEALED AND DATED BY THE
 COMPANY ENGINEER AND BY THE ARCHITECT
 OF RECORD. PROVIDE LEGIBLE FORMS).
 15-SEE ADDTIONAL COMMENTS ON PLANS,
 INCLUDING COMMENTS BY THE OTHER TRADES
 16-HIGHLIGHT FASTENING METHOD AND SYSTEM
 TO BE USED IN ROOF TILE PRODUCT APP'L.
  
  
  
 NOTE:
 -PLEASE RETURN REVIEWED SET OF PLANS
 AFTER CORRECTIONS ARE DONE TO THE
 ORIGINAL DRAWINGS IN ORDER TO EXPEDITE
 THE REVIEW PROCESS.