2001-01-08 00:00:00 | CHECKLIST: |
| 1-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| 2-REVISE LOAD REQUIREMENTS FOR ATTIC |
| STORAGE. 30 PSF LIVE LOAD. SEE TABLE |
| 1604.1 SBC 1997. |
| 3-PROVIDE SAFETY GLASS AS REQUIRED AT |
| FAMILY ROOM, LIVING ROOM AND MASTER |
| BATH. SECTION 2405.2 SBC 1997. |
| 4-PROVIDE COMPLETE AHU HANGING DETAILS. |
| INCLUDE FASTENERS TYPES AND SIZES. |
| DETAIL SHOWN ON SHEET A5 DOESN'T APPLY |
| TO THIS HOUSE. SECTION 104.2.2 CITY |
| AMENDMENTS TO SBC 1997. |
| 5-PROVIDE COMPLETE SPECIFICATIONS/DETAIL |
| FOR CEILING CONSTRUCTION AT ENTRY AND |
| REAR PORCHES. INCLUDE FASTENERS TYPES |
| AND SPACING. SECTION 2504 SBC 1997. |
| 6-FOOTING F2 TO HAVE 16" MINIMUM IN |
| DEPTH AS PER SECTION 1804.1.9 OF CITY |
| AMENDMENTS AND SEC. 1804.1.3 SBC 1997. |
| 7-ROOF FRAMING PLAN: SOME TRUSS GIRDERS |
| ARE SHOWN WITHOUT A SUPPORTING POST TO |
| TRANSFER THE LOAD TO THE FOOTING. |
| SPECIFY POSTS AND TOP AND BOTTOM |
| CONNECTORS. VERIFY IF CONCRETE PAD |
| REQUIRED TO CARRY THE LOAD. |
| SECTION 104.2.2 CITY AMENDMENTS. |
| 8-PROVIDE DETAIL/SPECS SHOWING HOW ARE |
| OPENINGS DESIGNED TO RECEIVESTORM |
| PANELS. DRAWINGS SHOW PRECAST LINTELS, |
| BUT WHAT ABOUT WINDOW SILLS? |
| THIS WILL DETERMINE THE TYPE OF ANCHOR |
| AND SPACING REQUIRED TO INSTALL THE |
| STORM PANEL. |
| 9-PROVIDE COMPLETE DETAIL/SPECS FOR |
| CONSTRUCTION OF ARCHED OPENINGS. |
| SECTION 104.2.2 CITY AMENDMENTS. |
| 10-PROVIDE SURVEY SHOWING NEW BUILDING |
| LAYOUT. |
| 11-PROVIDE SOIL TEST REPORT AS PER SEC. |
| 1804.2.7.3 OF CITY AMENDMENTS. |
| 12-PROVIDE COMPLETE BUCK DETAILS FOR |
| INSTALLATION OF DOORS AND WINDOWS. |
| INCLUDING THE STRUCTURAL BUCK DETAIL |
| FOR GARAGE DOORS AND SGD POCKET TYPE. |
| NOTE: SEE PRODUCT APPROVALS FOR |
| REQUIRED BUCK SIZE. |
| 13-STORM PANELS: |
| -CLARIFY WHICH PRODUCT APPROVAL IS |
| GOING TO BE USED. SBCCI OR DADE COUNTY |
| AND PROVIDE COMPLETE DRAWINGS FOR |
| EITHER ONE. |
| -SBCCI PRODUCT APPROVAL REPORT AND |
| DRAWINGS DON'T MATCH. SEE PAGE TWO OF |
| PRODUCT APPROVAL FOR APPROVED DRAWINGS |
| -PROVIDE A COMPLETE INSTALLATION SCHED. |
| AS PER CITY SAMPLE ATTACHED AND KEY |
| PLAN. |
| NOTE: KEEP IN MIND THAT ANCHOR TYPE |
| AND SPACING IS TO BE SELECTED ACCORD'G |
| TO THE DESIGN PRESSURES,EDGE DISTANCE, |
| PANEL SPAN, MEAN ROOF HEIGHT,CONNECT'N |
| TYPE AND STRUCTURE TO BE ATTACHED TO. |
| (THIS BUILDING IS MASONRY CONSTRUCTION |
| NOT 3000PSF CONCRETE). |
| 14-PROVIDE CURRENT PRODUCT APPROVAL FOR: |
| BUTT GLAZING SYSTEM AS SHOWN ON PLANS, |
| GARAGE DOORS (DADE COUNTY OR SBCCI, NO |
| BROWARD COUNTY), SLIDING GLASS DOORS |
| (POCKET TYPE AS SHOWN ON PLANS), FIXED |
| WINDOWS OF SIZES AS SHOWN ON LIVING RM |
| AND FAMILY RM,WINDOW MULLIONS, ARCHED |
| WINDOWS, ENTRY DOORS (IF SITE SPECIFIC |
| THEN THE PRODUCT APPROVAL FORM SHALL |
| BE SIGNED, SEALED AND DATED BY THE |
| COMPANY ENGINEER AND BY THE ARCHITECT |
| OF RECORD. PROVIDE LEGIBLE FORMS). |
| 15-SEE ADDTIONAL COMMENTS ON PLANS, |
| INCLUDING COMMENTS BY THE OTHER TRADES |
| 16-HIGHLIGHT FASTENING METHOD AND SYSTEM |
| TO BE USED IN ROOF TILE PRODUCT APP'L. |
| |
| |
| |
| NOTE: |
| -PLEASE RETURN REVIEWED SET OF PLANS |
| AFTER CORRECTIONS ARE DONE TO THE |
| ORIGINAL DRAWINGS IN ORDER TO EXPEDITE |
| THE REVIEW PROCESS. |