Plan Review Notes
Plan Review Notes For Permit 00061555
Permit Number 00061555
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SHOW VENT THROUGH ROOF.SPC SEC.904.3.1.
  
 WATER CLOSETS NOT PERMITTED ON WET VENTS
 COUNTYWIDE AMENDMENTS TO SPC SEC.911.1.1
  
 SHOW SIZE OF EXISTING SOIL STACK.
  
 CLEANOUTS SHALL BE INSTALLED PER SPC
 SEC.710.2.1.
  
 INDICATE SLOPE OF PIPE.COMPLY W/SPC
 TABLE 714.2.