Plan Review Notes For Permit 00061498 |
Permit Number |
00061498 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1) PROVIDE FIRE ALARM SYSTEM SHOP | | DRAWINGS FOR FIRE ALARM EQUIPMENT SHOWN | | IN TENANT SPACE. PLANS AND PERMIT | | REQUIRED. | | 2) EXITING PERMITTED THROUGH STOCKROOM | | IF THE FOLLOWING CONDITIONS EXIST, | | NOT MORE THAN 50 PERCENT OF EXIT ACCESS | | ALLOWED THROUGH STOCKROOM, DOOR CANNOT | | BE SUBJECT TO LOCKING, AISLE IN | | STOCKROOM TO EXIT MUST BE AT LEAST 44" | | WIDE, AISLE TO BE MAINTAINED AT THE | | 44" WIDTH. | | 3) PORTABLE FIRE EXTINGUISHERS REQUIRED. |
|