Plan Review Notes
Plan Review Notes For Permit 00061481
Permit Number 00061481
Review Stop FIRE
Sequence Number 3
Notes
Date Text
2001-04-26 00:00:001) PLANS DO NOT INDICATE THE VOLUME,
 HEIGHT OR WIDTH OF THE TANK. IT IS
 PRESUMED THAT THE TANK WILL CONTAIN
 LIQUID OXYGEN. PLEASE PROVIDE ELEVATION
 DRAWINGS OF THE OXYGEN TANK.
 2) NO PIPING OR APPURTENANT EQUIPMENT
 SHOWN TO OR FROM THE TANK.
 3) NO WARNING SIGNS OR LABELS
 IDENTIFYING THE HAZARD OR MATERIAL
 THAT IS PLANNED FOR STORAGE.
 4) NO SITE PLAN PROVIDED FOR THE
 INSTALLATION AREAS.
 5) ON THE PREVIOUS APPROVED PLANS THE
 TWO DOORS LEADING INTO THE SCREEN
 ENCLOSURE WERE DESIGNATED AS EXIT DOORS.
 PLEASE EXPLAIN EXITING ARRANGEMENT.
 6) THE SCREEN ENCLOSURE HAS NO PERMIT
 TO BE CONSTRUCTED. ALL EXTERIOR WORK
 WAS TO BE DONE UNDER SEPARATE PERMIT.
 7) WHERE DID THE ORIGINAL PROPOSED
 NITROGEN TANK GO.
  
 CAPTAIN MIKE CARSILLO
 659-8096,EXT.8497
 835-2910