Plan Review Notes For Permit 00061481 |
Permit Number |
00061481 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ****************PROVISO***************** | | 1)SHT A3.1-BACKFLOW PREVENTERS LOCATED | | IN VAULTS SHALL COMPLY W/SPC SEC.606.4.1 | | LOCATION SHALL BE APPROVED BY UTILITIES | | DEPT. | | | | 2)OVERFLOW DRAINAGE SYSTEM FOR THE ROOF | | SHALL BE DESIGNED ON 1994 EDITION OF THE | | SPC SEC.1109 & APPENDIX "A". | | | | 3)STORM WATER SYSTEM SHALL BE SHOWN ON | | CIVIL DRAWINGS AND SIZED PER TABLES | | 1108.1 & 1108.2 OF THE SPC. | | | | *****NOTE:REVISED DRAWINGS SHALL BE | | SUBMITTED PRIOR TO ISSUANCE OF PLUMBING | | PERMIT. |
|