Plan Review Notes For Permit 00061481 |
Permit Number |
00061481 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | FIRE DEPARTMENT CONNECTION SHALL BE | | LOCATED ADJACENT TO MAIN ENTRANCE. | | STAIR DETAILS SHALL BE IN COMPLIANCE | | WITH NFPA,1985 LIFE SAFETY CODE. | | PROVIDE TAMPER SWITCHES FOR DOUBLE OW | | DETECTOR CHECK. | | FIRE ALARM SYSTEM SHALL BE CLASS "A" OR | | ADDRESSABLE. | | FIRE DEPARTMENT CONNECTION SHALL BE | | LOCATED NEAR DRIVEWAY AND FACING | | DIRECTION OF DRIVEWAY |
|