Plan Review Notes For Permit 00061481 |
Permit Number |
00061481 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | *************** PROVISO *************** | | | | 1)NOTE: PLEASE SUBMIT REVISED LOAD | | CALCULATIONS SHOWING ALL CONTINUOUS | | LOADS AT 125% (LIGHTING ETC ) 220 NEC. | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | REVIEW BEFORE FINAL ELETRICAL INSPECT- | | -ION IS CALLED IN. IF THERE ARE ANY | | QUESTIONS PLEASE CALL. | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH | | 659-8096 EXT 8372 |
|