Plan Review Notes For Permit 00061476 |
Permit Number |
00061476 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | **************PROVISO******************* | | 1)BACKFLOW PREVENTERS LOCATED IN VAULTS | | SHALL COMPLY W/SPC SEC.606.4.1.-606.4.3 | | | | 2)OVERFLOW DRAINAGE FOR THE ROOF SHALL | | BE DESIGNED ON 1994 EDITION OF THE SPC | | SEC.1109 & APPENDIX "A". | | | | 3)STORM WATER SYSTEM SHALL BE SHOWN ON | | THE CIVIL DRAWINGS AND SIZED PER TABLES | | 1108.1 & 1108.2 OF THE SPC. | | | | ******NOTE:REVISED DRAWINGS SHALL BE | | SUBMITTED PRIOR TO ISSUANCE OF PLUMBING | | PERMIT. |
|