2001-01-08 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-THERE IS A SLIGHT CHANGE IN THE ROOF
 FRAMING PLAN BY THE MASTER BEDROOM
 SITTING AREA. SPECIFY ANCHORS AS
 REQUIRED FOR NEW TRUSS LAYOUT.
 2-CONNECTORS SPECIFIED FOR SOME ROOF
 TRUSSES DON'T RESIST THE UPLIFT LOADS
 CALCULATED IN THE ENGINEERED TRUSSES.
 REVISE CONNECTOR SCHEDULE AS REQUIRED.
 SEE TRUSS LAYOUT FOR COMMENTS.