Plan Review Notes
Plan Review Notes For Permit 00061167
Permit Number 00061167
Review Stop P
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00SUBMIT SANITARY AND WATER ISOMETRICS FOR
 REVIEW.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 SHOWER SHALL COMPLY W/FACBC FOR CONTROL
 MOUNTING HEIGHT,GRAB BARS,& SPRAY UNIT.
 CURBS ARE NOT PERMITTED IN SHOWERS THAT
 MEASURE MIN.30"X 60".PER FACBC SEC.
 4.21.2-4.21.7.
  
 SUBMIT RISER FOR NEW 2"WASTE FOR TRENCH
 DRAIN.COUNTYWIDE AMENDMENTS TO SPC SEC.
 104.2.1.
  
 IF TRENCH DRAIN WILL COLLECT CHEMICALS
 A NEUTRALIZATION TANK WILL BE REQUIRED
 PER SPC SEC.701.5,701.7,801.4.
  
 IF YOU HAVE ANY QUESTIONS I CAN BE
 REACHED AT 561-659-8096,EXT.8377.