2001-01-08 00:00:00LAYOUT OF TOILET ROOMS ON SHT.A9.1 DOES
 NOT CORRELATE W/THE REST OF THE PLANS.
  
 2)THE OCCUPANT LOAD OF 148 PEOPLE NOTED
 ON SHT.A9.1 REQUIRES 4 W.C'S FOR MALES
 AND FEMALES AND 2 LAVS.IN EACH RESTROOM.
 (TABLE 407 REQS.ARE FOR TOTAL NUMBER OF
 PERSONS.)
  
 3)THE SIZE OF THE HANDICAP STALLS DON'T
 COMPLY W/FACBC SEC.4.17.3.REVISE PLANS
 TO COMPLY.
  
 4)A VENT IS REQD.DOWNSTREAM OF ALL
 FIXTURES ON THE GREASY WASTE SYSTEM PER
 SPC SEC.921.
  
 5)A UNION IS REQD.DOWNSTREAM OF SHUTOFF
 VALVE PER NFPA 5.5.4.