Plan Review Notes For Permit 00061141 |
Permit Number |
00061141 |
|
Review Stop |
P |
Sequence Number |
4 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | LAYOUT OF TOILET ROOMS ON SHT.A9.1 DOES | | NOT CORRELATE W/THE REST OF THE PLANS. | | | | 2)THE OCCUPANT LOAD OF 148 PEOPLE NOTED | | ON SHT.A9.1 REQUIRES 4 W.C'S FOR MALES | | AND FEMALES AND 2 LAVS.IN EACH RESTROOM. | | (TABLE 407 REQS.ARE FOR TOTAL NUMBER OF | | PERSONS.) | | | | 3)THE SIZE OF THE HANDICAP STALLS DON'T | | COMPLY W/FACBC SEC.4.17.3.REVISE PLANS | | TO COMPLY. | | | | 4)A VENT IS REQD.DOWNSTREAM OF ALL | | FIXTURES ON THE GREASY WASTE SYSTEM PER | | SPC SEC.921. | | | | 5)A UNION IS REQD.DOWNSTREAM OF SHUTOFF | | VALVE PER NFPA 5.5.4. |
|