Plan Review Notes
Plan Review Notes For Permit 00061141
Permit Number 00061141
Review Stop E
Sequence Number 4
Notes
Date Text
2001-01-31 00:00:00*********** REVISION NEEDED
 ************1) NOTE: PLEASE NOTE THAT A
 MAIN DSCONNECT HAS BEEN ADDED TO PLANS
 ON SHEET E-5 FOR PANEL "K". NO SPECS
 WERE SUBMITTED
 FOR THIS EQUIPMENT. PLEASE DO SO.
 NOW THAT THERE IS A MAIN INLINE FROM
 TRANSFORMER, DOES PANEL "K " STILL HAVE
 A ,MAIN?
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW EQUIPMENT BEING INSTALLED.
 MAINS/PANELS/BREAKERS MUST BE RATED FOR
 THE AVAILABLE FAULT CURRNET PER 110-9.
 THIS IS REQ`D FOR NEW PANEL "K " DISC.
  
 3)NOTE: PLANS HAVE BEEN REDRAWN BY HAND
 AND NEEDS TO BE RE-DONE UNDER
 ADMINISTRATIVE CODE BEING SUBMITTED FOR
 RECORD.
 SEE SECTION 104.2.1 AND 104.2.7 FOR
 QUALITY OF PLANS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL. PLANS ARE FOR A"T.C.O"
 AND
 MUST BE DONE BEFORE"C.O.".
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-659-8096 EXT 8372