Date |
Text |
2001-01-08 00:00:00 | HANDICAP STALLS ARE REQUIRED IN THE |
| MALE AND FEMALE TOILET ROOMS PER FACBC |
| SEC.4.1.2.(6),4.17.3,4.22.4. |
| |
| LAVATORIES ARE REQD.IN THE HANDICAP |
| STALLS PER FACBC SEC.4.17.3.AND SIZE |
| SHALL COMPLY W/FACBC SEC.4.17.3. |
| |
| SHOW THE REQUIRED WHEELCHAIR TURNING |
| SPACE IN THE TOILET ROOMS PER FACBC SEC. |
| 4.2.3. |
| |
| HEIGHT OF URINAL SHALL COMPLY W/FACBC |
| SEC.4.18.2. |
| |
| SHT.P-1-FLOOR DRAINS AND FLOOR SINKS |
| ARE NOT PROPERLY VENTED PER SPC SEC. |
| 901.2,TABLE 908.1. |
| |
| SHT.P-3-VENT SIZING SHALL COMPLY W/SPC |
| TABLE 920.2.(DETERMINE BY FIXTURE UNIT |
| LOAD.) |
| |
| DISHWASHER SHALL DISCHARGE TO THE |
| SANITARY SYSTEM PER CITY OF WPB |
| ORDINANCE. |
| |
| A UNION IS REQD.ON THE GAS CONTROLS PER |
| NFPA 54 SEC.5.5.4. |
| |
| SUBMIT COPY OF/OR MAKE REFERENCE TO THE |
| APPROPRIATE GAS SIZING TABLE USED TO |
| DESIGN THE GAS SYSTEM.COMPLY W/ SGC SEC. |
| 305.4. |
| |
| INDICATE TYPE OF PIPING MATERIAL USED |
| FOR THE GAS SYSTEM.COMPLY W/SGC SEC.306. |
| |
| RECALCULATE THE BTU LOAD.MY CALCULATIONS |
| ARE 201,198.PLEASE VERIFY.SGC 305.3. |
| |
| SUBMIT LEGEND FOR ALL FIXTURES NOTED BY |
| NUMBERS ON SHT.P-4.COUNTYWIDE AMENDMENTS |
| TO SPC SEC.104.2.1. |
| |
| OVER 2 FIXTURES SUPPLIED BY 1/2"C.W.& |
| OVER 4 FIXTURES SUPPLIED BY 1/2" H.W. |
| PER COUNTYWIDE AMENDMENTS TO SPC SEC. |
| 607.7 |
| |
| SHT.P-5-NOTE #14-PIPING INSULATION SHALL |
| COMPLY W/F.E.C. TABLE 4-11. |
| |
| SUBMIT MANUF.SHEETS FOR GAS EQUIPMENT. |
| EQUIPMENT SHALL BE APPROVED PER SGC SEC. |
| 402.1.,501.2. |
| |
| GARBAGE DISPOSAL SHALL DISCHARGE TO THE |
| SANITARY PER 1004.11. |
| |
| SUBMIT ADDITIONAL INFORMATION FOR THE |
| WATER HEATER FLUE.INSTALLATION SHALL |
| COMPLY W/STANDARD GAS AND STANDARD |
| MECHANICAL CODES.(1997 EDITION.) |