Plan Review Notes
Plan Review Notes For Permit 00061141
Permit Number 00061141
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00ACCEPTED FOR AIR CONDITIONING
 PROVIDE MORE INFORMATION ON :
 WATER HEATER FLUE; LENGTH TI HGT ?
 PIZZA OVEN EXHAUST CAPACITY (LOAD)
 FIRE DAMPERS TO BE LOCATED AT SHAFT WALL
 FOR DUCTS ENTERING SHAFT
 GREASE DUCT ENCLOSURE TO BE FOR A SINGLE
 EXHAUST DUCT AND FOR NO OTHER PURPOSE
 DUCT REQUIRES MIN. 6" CLEARANCE FROM
 INSIDE OF ENCLOSURE
 PROVIDE INFORMATION ON ABOVE PRIOR TO
 MECH WORK ON THESE SYSTEMS
 SEPARATE PERMIT REQUIRED FOR HOOD, WALK
 IN COOLER/FREEZER AND FIRE SUPPRESSION
 SUBMIT PLANS AT TIME OF PERMIT APPLICA-
 TION FOR THESE SYSTEMS