Plan Review Notes For Permit 00061141 |
Permit Number |
00061141 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ACCEPTED FOR AIR CONDITIONING | | PROVIDE MORE INFORMATION ON : | | WATER HEATER FLUE; LENGTH TI HGT ? | | PIZZA OVEN EXHAUST CAPACITY (LOAD) | | FIRE DAMPERS TO BE LOCATED AT SHAFT WALL | | FOR DUCTS ENTERING SHAFT | | GREASE DUCT ENCLOSURE TO BE FOR A SINGLE | | EXHAUST DUCT AND FOR NO OTHER PURPOSE | | DUCT REQUIRES MIN. 6" CLEARANCE FROM | | INSIDE OF ENCLOSURE | | PROVIDE INFORMATION ON ABOVE PRIOR TO | | MECH WORK ON THESE SYSTEMS | | SEPARATE PERMIT REQUIRED FOR HOOD, WALK | | IN COOLER/FREEZER AND FIRE SUPPRESSION | | SUBMIT PLANS AT TIME OF PERMIT APPLICA- | | TION FOR THESE SYSTEMS |
|