Plan Review Notes For Permit 00061127 |
Permit Number |
00061127 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | SUBMIT CALCULATIONS FOR PRIMARY STORM | | DRAINAGE SYSTEM TO ENSURE THAT PIPING | | BEING INSTALLED AT THIS TIME IS SIZED | | PROPERLY FOR THE SQUARE FOOTAGE OF THE | | ROOF.COUNTYWIDE AMENDMENTS TO SPC 104.2. | | & SPC SEC.1108.1,1108.2. | | | | SUBMIT PIPING ISOMETRIC AND CALCULATIONS | | FOR THE STORM DRAINAGE SYSTEM IN THE | | PARKING GARAGE IF IT WILL BE COVERED | | UNDER THIS PERMIT.AMENDMENTS TO SPC | | SEC.104.2.1.,1108.1,1108.2. |
|