2001-01-08 00:00:00 | **************** PROVISO *************** | | | | 1)NOTE: PLEASE SEE ORIG. NOTES. THE | | DIMMER SCHEDULE SHOWS SWITCH #6 FOR | | FIXTURE "X" WHICH IS SHOWN AS EXIT SIGN. | | SWITCHING THE EXIT SIGN IS NOT PERMITTED | | IF THIS IS NOT THE CASE PLEASE CLARIFY. | | | | 2)NOTE: PLEASE SEE AND NOTE THAT ON E-1 | | YOU SHOW TWO WATER HEATERS @ 3500W? YET | | THE LOAD CALCULATION SHOWS A TOTAL OF | | 4800W? PLEASE CHECK AND RE-DO. | | | | 3)NOTE: PLEASE SEE E-2. THE SHOW WINDOW | | LIGHTING IS SHOWMN AT .4 KVA. AND ON | | E-1 ITIS SHOWN AT .45 KVA. 125% OF | | .4 IS NOT .45. PLEASE VERIFY. | | | | 4)NOTE: PLEASE SUBMIT THE AIC RATINGS OF | | THE DISCONNECTS. IT APPEARS THAT THEY | | ARE FUSED DISC. PLEASE GIVE FUSE TYPE. | | | | | | 5)NOTE: AS BEFORE; PLEASE SHOW DIMMER | | LOCATION ON PLANS. | | | | | | PLEASE SUBMIT ALL THE ABOVE INFORMATION | | FOR REVIEW BEFORE ANY ROUGH ELECTRICAL | | INSPECTION IS CALLED IN. | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | 561-659-8096 EXT 8372 | | | | DEWEY PALMER | | ELECTRICAL PLAN REVIEW | | CITY OF WEST PALM BEACH |
|