Plan Review Notes
Plan Review Notes For Permit 00061076
Permit Number 00061076
Review Stop E
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:00**************** PROVISO ***************
  
 1)NOTE: PLEASE SEE ORIG. NOTES. THE
 DIMMER SCHEDULE SHOWS SWITCH #6 FOR
 FIXTURE "X" WHICH IS SHOWN AS EXIT SIGN.
 SWITCHING THE EXIT SIGN IS NOT PERMITTED
 IF THIS IS NOT THE CASE PLEASE CLARIFY.
  
 2)NOTE: PLEASE SEE AND NOTE THAT ON E-1
 YOU SHOW TWO WATER HEATERS @ 3500W? YET
 THE LOAD CALCULATION SHOWS A TOTAL OF
 4800W? PLEASE CHECK AND RE-DO.
  
 3)NOTE: PLEASE SEE E-2. THE SHOW WINDOW
 LIGHTING IS SHOWMN AT .4 KVA. AND ON
 E-1 ITIS SHOWN AT .45 KVA. 125% OF
 .4 IS NOT .45. PLEASE VERIFY.
  
 4)NOTE: PLEASE SUBMIT THE AIC RATINGS OF
 THE DISCONNECTS. IT APPEARS THAT THEY
 ARE FUSED DISC. PLEASE GIVE FUSE TYPE.
  
  
 5)NOTE: AS BEFORE; PLEASE SHOW DIMMER
 LOCATION ON PLANS.
  
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW BEFORE ANY ROUGH ELECTRICAL
 INSPECTION IS CALLED IN.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 561-659-8096 EXT 8372
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH