Plan Review Notes
Plan Review Notes For Permit 00061076
Permit Number 00061076
Review Stop M
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00DENIED*******************************
 1. PROVIDE OUTSIDE CALCULATIONS PER
 ASHRAE 62-89.
 2. REQUIRES AIR BALANCE SCHEDULE TO SHOW
 COMPLIANCE WITH 1997 SMC 501.2.
 3. NFPA 90A REQUIRES NOTICATION OF
 ACTIVATION OF DUCT SMOKE DETECTOR BY
 VISUAL AND AUDIBLE SIGNAL. THIS IS
 NOT REQUIRED TO BE TIED IN TO THE
 MALL FIRE ALARM SYSTEM.