Plan Review Notes
Plan Review Notes For Permit 00061076
Permit Number 00061076
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00******************* UNSAT **************
  
 1)NOTE: PLEASE SHOW ALL DIMMER/SWITCH
 LOCATIONS.
  
 2)NOTE: PLEASE NOTE THAT EXIT LIGHTS ARE
 SHOWN ON SWITCH #6??? THIS IS NOT
 PERMITTED AND EMERGENCY LIGHTS ALSO.
  
 3)NOTE:PLEASE NOTE THAT LOAD OF TRACK
 LIGHTING NEEDS TO BE SHOWN SEPARATE
 IN CALCULATIONS.ALSO AT 125% FOR CONTIN-
 UOUS LOAD.22-12
  
 4)NOTE:SHOW WINDOW IS SHOWNON PANEL AT
 .4 KW AND ON LOAD CALCS AT .45KW?
 PLEASE CORRELATE
  
 5)NOTE:PLEASE SUBMIT AIC RATING OF MAIN
 DISCONNECTS.MAINS//PANLES ARE TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT
 PER 110-9/215-5
  
 ^0NOTE:LIGHTING IS SHOWN ON LOAD CALCS
 AT 1,630,,,3W-PER-SQ-AT 125% YOU SHOW
 TOTAL AT 4,890? PLEASE SHOW,,,I COME UP
 WITHA DIFFERENT TOTAL.
  
 7)NOTE:PLEASE SEE LOAD CALCS,,YOU SHOW
 LOADS FOR WATER HEATERS AT 3500 EACH
 AND DIFFERENT TOTAL LOAD?? THIS ALSO
 DOES NOT CORRELATE WITH PANEL SCHEDLUE?
  
 PLEASE SUBMIT ALL THE ABOVE INFORMATION
 FOR REVIEW. IF THERE ARE ANY QUESTIONS
 PLEASE CALL 561-659-8096 EXT 8372
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW