Plan Review Notes
Plan Review Notes For Permit 00061010
Permit Number 00061010
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2001-01-08 00:00:001) ALL EXIT DOORS SHALL SWING IN THE
 DIRECTION OF EXIT TRAVEL.
 2) ALL EXIT DOORS SHALL BE EQUIPPED WITH
 APPROVED PANIC HARDWARE.
 3) OCCUPANT LOAD TO BE DETERMINED BY THE
 FIRE RESCUE DEPARTMENT.
 4) INTERIOR FINISH IN EXITS TO BE CLASS
 A OR B.
 5) ALL STORAGE ROOMS IF ANY ARE TO BE
 FIRE SEPARATED BY AT LEAST ONE HOUR
 FIRE RATING.
 6) PRIOR TO OCCUPANCY, INSPECTIONS ARE
 TO BE PERFORMED BY FIRE RESCUE.
 APPROVED PROVISO: