Plan Review Notes
Plan Review Notes For Permit 00060937
Permit Number 00060937
Review Stop R
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00CHECKLIST:
 1-BATH AT FIRST FLOOR TO HAVE DOOR THAT
 PROVIDES A 29" MINIMUM CLEAR OPENING.
 CHAPTER 11 OF FLORIDA ACCESSIBILITY
 CODE FOR BUILDING CONSTRUCTION, 1997.
 2-PROVIDE PRODUCT APPROVAL FROM SBCCI OR
 DADE COUNTY FOR ALL WINDOWS, INCLUDING
 THE OCTAGON WINDOW, OR SITE SPECIFIC
 ENGINEERING FOR EACH HOUSE.
 -SLIDING GLASS DOORS: PROVIDE COPIES OF
 TESTS RESULTS AS PER ASTM E 330.
 SECTION 1706 SBC 1997.
 PROVIDE SITE SPECIFIC ENGINEERING.
 3-ENTRY DOOR PRODUCT APPROVAL HAS
 EXPIRED.
 -PROVIDE COPIES OF APPROVED DWGS ALSO.
 4-REVISE/UPDATE DRAWINGS SEE COMMENTS ON
 PLANS.
 5-POVIDE SOIL TESTS REPORT AS PER CITY
 AMENDMENTS SECTION 1804.2.7.3.
 6-PROVIDE UPDATE PRODUCT APPROVAL FOR
 STORM PANELS. THE ONE SUBMITTED IS
 ABOUT TO EXPIRE.
  
 NOTES:
 -SEE COMMENTS BY OTHER TRADES.
 -PLEASE RETURN REVIEWED SET IN ORDER
 EXPEDITE THE REVIEW PROCESS.
 -TOTAL CALCULATED VALUATION IS $118,803.
 CALCULATED AS FOLLOWS:
 $69.69 $/SF FOR A/C AREAS AND
 $36.40 $/SF FOR NON A/C AREAS.