Plan Review Notes For Permit 00060937 |
Permit Number |
00060937 |
|
Review Stop |
R |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | CHECKLIST: | | 1-BATH AT FIRST FLOOR TO HAVE DOOR THAT | | PROVIDES A 29" MINIMUM CLEAR OPENING. | | CHAPTER 11 OF FLORIDA ACCESSIBILITY | | CODE FOR BUILDING CONSTRUCTION, 1997. | | 2-PROVIDE PRODUCT APPROVAL FROM SBCCI OR | | DADE COUNTY FOR ALL WINDOWS, INCLUDING | | THE OCTAGON WINDOW, OR SITE SPECIFIC | | ENGINEERING FOR EACH HOUSE. | | -SLIDING GLASS DOORS: PROVIDE COPIES OF | | TESTS RESULTS AS PER ASTM E 330. | | SECTION 1706 SBC 1997. | | PROVIDE SITE SPECIFIC ENGINEERING. | | 3-ENTRY DOOR PRODUCT APPROVAL HAS | | EXPIRED. | | -PROVIDE COPIES OF APPROVED DWGS ALSO. | | 4-REVISE/UPDATE DRAWINGS SEE COMMENTS ON | | PLANS. | | 5-POVIDE SOIL TESTS REPORT AS PER CITY | | AMENDMENTS SECTION 1804.2.7.3. | | 6-PROVIDE UPDATE PRODUCT APPROVAL FOR | | STORM PANELS. THE ONE SUBMITTED IS | | ABOUT TO EXPIRE. | | | | NOTES: | | -SEE COMMENTS BY OTHER TRADES. | | -PLEASE RETURN REVIEWED SET IN ORDER | | EXPEDITE THE REVIEW PROCESS. | | -TOTAL CALCULATED VALUATION IS $118,803. | | CALCULATED AS FOLLOWS: | | $69.69 $/SF FOR A/C AREAS AND | | $36.40 $/SF FOR NON A/C AREAS. |
|