Plan Review Notes For Permit 00060937 |
Permit Number |
00060937 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ****DENIED****************************** | | PROVIDE THE FOLLOWING INFORMATION: | | 1. MODEL NUMBER,MAKE AND SIZE OF ALL THE | | EXHAUST FANS REQUIRED. | | 2. LOCATION &SIZE OF THE CONDENSATE | | LINES 1997 SMC 304.8.3 | | 3. INDICATE THE LOCATION OF THE CONDEN- | | SATE UNIT. | | 4. SHOW THE LOCATION OF THE DRYER VENT. | | 1997 SMC 509.3 | | 5. PROVIDE CFM VALUE OF ALL A/C DROPS ON | | BOTH BUILDING ALSO THE DUCT SIZES. |
|