2001-01-08 00:00:00****DENIED******************************
 PROVIDE THE FOLLOWING INFORMATION:
 1. MODEL NUMBER,MAKE AND SIZE OF ALL THE
 EXHAUST FANS REQUIRED.
 2. LOCATION &SIZE OF THE CONDENSATE
 LINES 1997 SMC 304.8.3
 3. INDICATE THE LOCATION OF THE CONDEN-
 SATE UNIT.
 4. SHOW THE LOCATION OF THE DRYER VENT.
 1997 SMC 509.3
 5. PROVIDE CFM VALUE OF ALL A/C DROPS ON
 BOTH BUILDING ALSO THE DUCT SIZES.