Plan Review Notes
Plan Review Notes For Permit 00060937
Permit Number 00060937
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00************** UNSAT *******************
  
 1)NOTE: PLEASE LIST AIC RATING FOR ALL
 EQUIPMENT MAINS AND PANELS. MAINS AND
 PANELS ARE TO BE RATED FOR THE AVAILABLE
 FAULT CURRENT. PER 110-9.
  
 2)NOTE:PLEASE SHOW ALL OUTLETS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED. 210-8-A-6 SHOW IN BOTH UNITS.
  
 3)NOTE: PLEASE INCLUDE COPPER COLD
 WATER PIPE AS PART OF THE GROUNDING
 ELECTRODE SYSTEM. 250-50
  
 4)NOTE:PLEASE SHOW ON PANEL SCHEDULES
 THE REQ`D BATH(S) CIRCUIT(S) AS PER
 210-11-C-3. MUST BE SHOWN AS 20AMP AND
 #12 AWG..
  
 5)NOTE: PLEASE SHOW TWO SEPARATE PANEL
 SCHEDULES FOR THE TWO UNITS.
  
 6)NOTE: YOU SHOW 'TV BOX' NEXT TO THE
 METERCAN. PLEASE SHYOW THE DISCONNECT
 THAT YOU SHOW ON THE RISER DIAGRAM.
  
 PLEASE SUBMIT THE ABOVE FOR REVIEW.
 IF THERE ARE ANY QUESTIONS PLEASE CALL
 659-8096 EXT 8372