Plan Review Notes For Permit 00060937 |
Permit Number |
00060937 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | ************** UNSAT ******************* | | | | 1)NOTE: PLEASE LIST AIC RATING FOR ALL | | EQUIPMENT MAINS AND PANELS. MAINS AND | | PANELS ARE TO BE RATED FOR THE AVAILABLE | | FAULT CURRENT. PER 110-9. | | | | 2)NOTE:PLEASE SHOW ALL OUTLETS SERVING | | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- | | -ED. 210-8-A-6 SHOW IN BOTH UNITS. | | | | 3)NOTE: PLEASE INCLUDE COPPER COLD | | WATER PIPE AS PART OF THE GROUNDING | | ELECTRODE SYSTEM. 250-50 | | | | 4)NOTE:PLEASE SHOW ON PANEL SCHEDULES | | THE REQ`D BATH(S) CIRCUIT(S) AS PER | | 210-11-C-3. MUST BE SHOWN AS 20AMP AND | | #12 AWG.. | | | | 5)NOTE: PLEASE SHOW TWO SEPARATE PANEL | | SCHEDULES FOR THE TWO UNITS. | | | | 6)NOTE: YOU SHOW 'TV BOX' NEXT TO THE | | METERCAN. PLEASE SHYOW THE DISCONNECT | | THAT YOU SHOW ON THE RISER DIAGRAM. | | | | PLEASE SUBMIT THE ABOVE FOR REVIEW. | | IF THERE ARE ANY QUESTIONS PLEASE CALL | | 659-8096 EXT 8372 |
|