2001-01-08 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-ENGINEER NEEDS TO PROVIDE ORIGINAL
 SIGNATURE ON ALL DOCUMENTS SUBMITTED
 FOR PUBLIC RECORDS. SEE ATTACHED COPY
 OF FLORIDA STATUTES.
 2-UPDATE ENGINEERED TRUSS DRAWINGS.
 THERE ARE SEVERAL WIND LOAD ANALYSIS.
 SOME TRUSSES ARE DESIGNED USING SBC
 1997, OTHERS ARE DESIGNED USING ASCE
 7-93 AND OTHERS USING ASCE 7-95.
 THE CORRECT DESIGN CRITERIA SHOULD BE
 ASCE 7-95 FOR A WIND LOAD OF 145MPH
 AND A MEAN ROOF HEIGHT OF 17'-0".
 OR, SBC 1997 WITH 110 MPH WIND LOAD
 AND 17'-0" MEAN ROOF HEIGHT.
 3-UPDATE ALL GENERAL DETAILS AND SIGN,
 SEAL AND DATE THEM. NOTE: THERE SHOULD
 BE ONLY ONE ENGINEER RESPONSIBLE FOR
 SUCH DETAILS. CHAPTER 471 FL. STATUTES
 4-ARCHITECT TO REVISE ANCHOR SCHEDULE.
 -CONNECTORSSPECIFIED AT COVERED
 PORCHES ARE CONCRETE TO WD CONNECTORS.
 NEED A WOOD TO WOOD CONNECTOR AS
 REQUIRED.
 -CLEARLY SPECIFY CONNECTORS FOR ALL
 BEARING POINTS OF ENGINEERED TRUSSES.
 EG: SEE TRUSSES S1N, T22, S13, HH1.
 SEE ENGINEERED TRUSSES TO PROPERLY
 SPECIFY CONNECTOR THAT WILL RESIST THE
 CALCULATED LOADS.
 -ROOF FRAMING PLAN BY ARCHITECT NEEDS
 TO SPECIFY CONNECTORS AT ALL BEARING
 POINTS. SEE ROOF FRAMING PLAN AND
 CLEARLY SPECIFY MISSING CONNECTORS.