Plan Review Notes For Permit 00060760 |
Permit Number |
00060760 |
|
Review Stop |
R |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | TRUSS DRAWINGS CHECKLIST: | | 1-CONNECTORS SPECIFIED FOR TRUSS H6 | | DON'T RESIST THE LOADS CALCULATED BY | | TRUSS ENGINEER. REVISE CONNECTORS AS | | REQUIRED. | | 2-ALL GENERAL TRUSS DETAILS TO BE SEALED | | SIGNED AND DATED AS PER CHAPTER 471 OF | | FLORIDA STATUTES. | | 3-TRUSS DRAWING T2 NEEDS TO BE SIGNED, | | SEALED AND DATED. | | IN ADDITION, CLARIFY WHY THE LOADS | | CALCULATED ARE DONE BY HAND AND NOT | | RUN BY THE COMPUTER. ENGINEER TO | | CERTIFY THIS CHANGE. |
|