2001-01-08 00:00:00TRUSS DRAWINGS CHECKLIST:
 1-CONNECTORS SPECIFIED FOR TRUSS H6
 DON'T RESIST THE LOADS CALCULATED BY
 TRUSS ENGINEER. REVISE CONNECTORS AS
 REQUIRED.
 2-ALL GENERAL TRUSS DETAILS TO BE SEALED
 SIGNED AND DATED AS PER CHAPTER 471 OF
 FLORIDA STATUTES.
 3-TRUSS DRAWING T2 NEEDS TO BE SIGNED,
 SEALED AND DATED.
 IN ADDITION, CLARIFY WHY THE LOADS
 CALCULATED ARE DONE BY HAND AND NOT
 RUN BY THE COMPUTER. ENGINEER TO
 CERTIFY THIS CHANGE.