2001-01-08 00:00:00 | TRUSS DRAWINGS CHECKLIST: | | 1-REVISE MEAN ROOF HEIGHT.SEE ARCHITECTS | | DRAWINGS FOR CORRECT MEAN ROOF HEIGHT. | | 2-ARCHITECT TO REVISE ANCHOR SCHEDULE ON | | SHEET #8. SEE THE SEMCO CATALOGUE FOR | | THE ACTUAL VALUE THAT IS ENGINEERED | | FOR THE CONNECTORS SPECIFIED. | | 3-ARCHITECT TO SPECIFY ALL CONNECTORS. | | SEE ENGINEERED TRUSS DRAWINGS AND | | TRUSS LAYOUT FOR COMMENTS. | | NOTE: MAKE SURE TO SPECIFY WOOD TO | | WOOD OR CONCRETE TO WOOD CONNECTORS | | AS REQUIRED ACCORDING TO THE ACTUAL | | CONDITIONS. | | | | NOTES: | | -PLEASE RETURN REVIEWED SET AFTER | | CORRECTIONS ARE DONE IN ORDER TO | | EXPEDITE THE REVIEW PROCESS. | | -IF YOU HAVE ANY QUESTIONS, PLEASE | | CONTACT JULIO GOMEZ AT 659-8096 EXT. | | 8232. |
|