2001-01-08 00:00:00 | CHECKLIST: |
| 1-PROVIDE ENERGY CALCULATIONS. |
| 2-PAY IMPACT FEES TO PALM BEACH COUNTY. |
| 3-NEED A PERMIT APPLICATION FOR EACH |
| TOWNHOUSE. |
| 4-PROVIDE SAFETY GLASS WHERE REQUIRED. |
| SEE PLANS FOR COMMENTS. SEC 2405.2 SBC |
| 5-PROVIDE PRODUCT APPROVALS FOR: TWO HR |
| FIRE RATED CONCRETE BLOCK, SKYLIGHT, |
| WINDOW MULLIONS, SLIDING GLASS DOORS, |
| ARCHED WINDOWS AND SINGLE HUNG WINDOWS |
| WITH MUNTINS. (SEE COMMENTS ON FACE OF |
| PRODUCT APPROVALS SUBMITTED). |
| 6-ARCHITECT NEEDS TO DATE DRAWINGS WHEN |
| SIGNING AND SEALING DRAWINGS AND |
| DOCUMENTS FOR PUBLIC RECORDS. CHAPTER |
| 481.221(A0. |
| 7-PROVIDE COMPLETE FRAMING DETAILS FOR |
| SKYLIGHT INSTALLATION. SECTION 104.2.2 |
| CITY AMENDMENTS TO SBC 1997. |
| 8-COMPLETELY SPECIFY CEILING CONSTRUCT'N |
| AT ENTRY AND REAR PORCHES. INCLUDE |
| FASTENER TYPE AND SPACING. SECTION |
| 2504 SBC 1997. |
| 9-FLOOR PLAN DOESN'T MATCH ELEVATIONS. |
| SEE REAR ELEVATION. ALSO,UPDATE/REVISE |
| DRAWINGS AS REQUIRED. SEE COMMENTS ON |
| PLANS. |
| 10-REVISE BEAM SCHEDULE. SIZES DON'T |
| MATCH FLOOR PLANS. |
| 11-REVISE ROOF TRUSS ANCHOR SCHEDULE AS |
| REQUIRED. NEED TO SPECIFY WOOD TO WOOD |
| CONNECTOR AT PORCHES' BEAMS. |
| SECTION 104.2.2 CITY AMENDMENTS. |
| 12-PROVIDE PROFILE OF TWO HOUR DEMISING |
| WALL SHOWING LOCATION OF BEAMS AND |
| VERTICAL REINFORCEMENT. SECTION |
| 104.2.2 CITY AMENDMENTS. |
| 13-CLEARLY KEY ON PLANS ALL THE DETAILS |
| THAT APPLY TO THIS HOUSE AND DELETE OR |
| CROSS OUT THE ONES THAT DON'T. |
| |
| |
| NOTE: |
| PLEASE RETURN REVIEWED SET IN ORDER TO |
| EXPEDITE THE REVIEW PROCESS. |