Plan Review Notes
Plan Review Notes For Permit 00060179
Permit Number 00060179
Review Stop E
Sequence Number 1
Notes
Date Text
2001-01-08 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE SUBMIT REVISE AND RESUB
 PLANS WITH PANEL SCHEDULES AND RISER
 DIAGRAMS THAT MATCH. PLEASE CORRELATE
 WIRING/BRKRS/LOADS. I HAVE GIVEN THESE
 SAME NOTES BEFORE ON THE SAME THINGS.
  
 2)NOTE: YOUR ELETRICAL NOTES REF. CODES
 FROM THE '96' NEC. PLEASE USE '99' CODE
 FOR ARTS; REFERENCED.
  
 3)NOTE: PLEASE DRAW IN THE A/C CU AND
 THE REQ`D DISCONNECT AND GFI RECEPT.
 PER 440-11 AND 210-63
  
  
 PLEASE RE-SUB ALL THE ABOVE INFORMATION
 CORRECTED FOR REVIEW. IF THERE ARE ANY
 QUESTIONS PLEASE CALL 659-8096 EXT 8372