Plan Review Notes
Plan Review Notes For Permit 00060163
Permit Number 00060163
Review Stop P
Sequence Number 3
Notes
Date Text
2001-01-08 00:00:00***************PROVISO******************
 SUBMIT A SANITARY RISER THAT COMPLIES W/
 THE STANDARD PLUMBING CODE PRIOR TO
 INSPECTION.
 A)WATER CLOSETS NOT PERMITTED ON WET
 VENTS.COUNTYWIDE AMENDMENTS TO SPC SEC.
 911.1.1.
  
 B)CIRCUIT AND LOOP SYSTEM SHALL COMPLY
 W/SPC SEC.914.1,914.2,914.3.4,920.3,IF
 THAT IS THE INTENT OF THE DESIGN.I HAVE
 NO IDEA WHAT YOU ARE ATTEMPTING WITH THE
 SANITARY SYSTEM AS DRAWN.
  
 C)CLEARLY INDICATE ON THE PLAN WHERE
 SANITARY RISERS #5-8 CONNECT TO RISERS
 #1-4.COUNTYWIDE AMENDMENTS 104.2.1.
  
 D)CONDENSATE DRAIN SHALL BE EQUIPPED W/
 AN EMERGENCY OVERFLOW.
  
 CALL 561-659-8096,EXT.8377 IF YOU HAVE
 QUESTIONS.
 TIMOTHY LARGE
 PLUMBING PLANS EXAMINER