Plan Review Notes For Permit 00060163 |
Permit Number |
00060163 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2001-01-08 00:00:00 | 1)THE WAIVER FOR THE GREASE TRAP SHALL | | BE SIGNED BY R.COMPO.COUNTYWIDE AMEND- | | MENTS TO SPC SEC.101.4.7. | | | | 2)THE LOCATION OF THE HANDICAP | | FACILITIES ON SHT.P2.1 DOESN'T CORRELATE | | W/THE ARCHITECTURAL PLANS.CLARIFY. | | | | 3)THE SANITARY RISER SHALL CORRELATE W/ | | THE CORRECT FLOOR PLAN.COUNTYWIDE | | AMENDMENTS TO SPC SEC.104.2.1. | | | | 4)WATER CLOSETS ARE NOT PERMITTED ON WET | | VENTS PER COUNTYWIDE AMENDMENTS TO SPC | | SEC.911.1.1. | | | | 5)THE HABITABLE SQUARE FEET AND OCCUPANT | | SHALL BE ON THE PLANS.SPC SEC.407.1.3. | | | | 6)A DEP PERMIT IS REQD.FOR THE INSTALL- | | ATION OF THE WATER SYSTEMS.COUNTYWIDE | | AMENDMENTS TO SPC SEC.101.4.7. | | | | 7)AN EMERGENCY OVERFLOW IS REQD.ON THE | | CONDENSATE DRAIN TO THE DRYWELL. | | | | | | CALL 561-659-8096,EXT.8377 IF YOU HAVE | | ANY QUESTIONS. | | TIMOTHY LARGE | | PLUMBING PLANS EXAMINER. |
|